Most hospital engineering teams know the pattern. An odor complaint comes in from a nursing unit or a waiting area; the team changes filters and checks the ductwork, and the complaint goes away for a week before it returns. Meanwhile, a large air handling unit serving the same wing has been running its supply fan harder every month, and nobody has had a shutdown window to pull the coil apart. These two problems often share a starting point inside the air handler, and they tend to cost more the longer they go unaddressed.

Most of the work is diagnostic and procedural, which is where facility teams have the most control. Equipment can help with the parts that procedure alone can’t reach. One approach that has moved into hospital mechanical rooms is ionisation applied directly at the cooling coil, which GPS Air uses for HVAC coil cleaning and odor control in healthcare facilities as a continuous maintenance measure rather than a periodic cleaning event.

Where coil fouling starts

A cooling coil in a large hospital air handler spends much of the year wet. During cooling and dehumidification, moisture condenses on the fins and drains to the pan, and the wet surface collects whatever the filters let through. Fine dust, fibers, and organic material settle on the fin faces and between rows, and the combination of moisture and debris builds into a film that thickens over time.

Deep coils make the problem harder to see. A six- or eight-row coil can look acceptable on its entering face while the interior rows carry significant buildup. Surface inspection with a flashlight tells an engineer very little about what is happening a few inches in.

Hospitals add operating conditions that accelerate fouling. Many air handlers run around the clock because the spaces they serve have continuous pressure, temperature, and humidity requirements. Long condensing hours mean the coil stays wet longer. Outdoor air volumes in healthcare are high compared with most commercial buildings, so the coil handles more incoming moisture and particulate.

Where persistent odor comes from

Odor complaints in hospitals are frequently misdiagnosed because the instinct is to look inside the building. Filters get changed, diffusers get cleaned, and the complaint returns because the source was never addressed.

In many facilities, the source is outside. Helicopter pads, loading docks, truck delivery areas, trash and waste holding areas, and generator exhaust are often located close to outdoor air intakes, particularly on campuses that have expanded over several decades. Diesel fumes, jet fuel exhaust and waste odors are drawn into the intake, pass through the filters as gases and vapors, and travel with the supply air to occupied floors. Particulate filters are designed to capture particles. Odor-causing molecules in the gas phase largely pass through them, so filter changes don’t resolve this kind of complaint.

The coil itself can also contribute. A fouled, wet coil surface produces its own odor, which reaches the space every time the unit runs. When the coil and an outdoor source are both contributing, a team that addresses only one of them sees partial improvement and concludes the fix didn’t work.

A practical diagnostic sequence helps separate the causes. Map complaint locations against the air handlers that serve them. Note whether complaints track with helicopter flights, delivery schedules, or wind direction, which points toward an intake source. Inspect the coil and drain pan of the affected unit, including interior rows where access allows. Review intake locations against nearby exhaust and odor sources, since relocating an intake or extending an exhaust stack is sometimes the right answer.

What fouled coils cost in energy and maintenance

Coil fouling raises the air-side pressure drop across the coil. To hold airflow, a fan on a variable frequency drive ramps up, and fan power rises with the added static pressure. A constant-speed fan simply delivers less air. Either way, the building pays, through higher fan energy or through degraded airflow that can push spaces away from their design conditions.

Heat transfer suffers too. Buildup on the fins insulates the coil surface, so the chilled water system works harder to reach the same leaving air temperature. In healthcare, where design relative humidity and temperature ranges are specified by space type, a coil that can’t dehumidify effectively becomes a compliance concern as well as an energy one.

The maintenance burden is often the larger cost. Cleaning a large coil thoroughly typically requires taking the unit offline or arranging temporary air, which is difficult for systems that serve spaces with continuous pressure relationships. Chemical cleaning and pressure washing can be effective on shallow coils, but on deep coils they can push debris further into the interior rows. Many hospitals end up cleaning less often than they would like because shutdown windows are scarce, and the coil degrades between cleanings.

The standards context facility teams work within

ANSI/ASHRAE/ASHE Standard 170-2025, Ventilation of Health Care Facilities, is the current edition of the ventilation standard for hospitals and other healthcare settings. It sets design requirements by space type, including pressure relationships, air change rates, minimum filter efficiencies, and design ranges for relative humidity and temperature. Authorities having jurisdiction enforce different editions of the standard, so teams should confirm which one applies to their facility before referencing a specific requirement.

Standard 170 is developed in coordination with the Facility Guidelines Institute. FGI released its 2026 edition in September 2026, renaming the documents the FGI Codes for Planning and Design, with companion FGI Handbooks. Most states adopt the FGI documents by reference for healthcare design and construction, again on varying schedules, and many facilities are still operating under the 2018 or 2022 Guidelines for Design and Construction.

For day-to-day operation, ASHRAE/ASHE Guideline 43, the Operations Guideline for Ventilation of Health Care Facilities, is the more relevant companion. It addresses how ventilation systems designed to Standard 170 should be operated and maintained over time. Coil condition fits squarely within that operational scope, since a fouled coil affects the airflow, humidity and temperature conditions the design was built to deliver.

ASHRAE Standard 241, Control of Infectious Aerosols, addresses a separate question about infection risk management, and it sits outside the scope of routine coil maintenance and odor control.

An on-coil approach as a maintenance and odor-control tool

Periodic cleaning restores a coil to a known condition. The harder problem is keeping it there between cleanings. Continuous treatment at the coil addresses that gap.

GPS-iMod®, part of GPS Air’s needlepoint bipolar ionisation (NPBI®) family, mounts directly to the cooling coil inside the air handling unit. It is field-assembled in 6-inch increments to match coil width and delivers soft ionisation evenly across the coil face during operation. GPS Air states that the system reduces the buildup that drives both pressure-drop increases and coil-generated odor, extending the interval between cleanings rather than replacing them. It has no replacement parts and does not require taking the unit offline for routine service.

On the odor side, ions reduce volatile organic compounds and odor-causing molecules, which is helpful in protecting indoor air from common odors, including exhaust, diesel fumes, smoke, and cooking smells. Because the treatment sits at the air handler, it acts on odor carried in with outdoor air before that air is distributed to occupied floors. It complements intake management and filtration rather than standing in for either.

For healthcare settings, safety credentials matter. GPS-iMod is UL 2998 validated for zero ozone emissions and is CARB-compliant, which is relevant for facilities in California and for any team that wants documented verification before installing equipment in a hospital air handler.

What a documented result looks like

A Novant Health facility offers a measured example. A 28,000 CFM custom air handling unit had been running at 100 percent fan demand for more than two years, with static pressure across the coil reaching approximately 3.5 inches of water column during condensing conditions. GPS-iMod was installed in August 2023 and energised the following month. According to the published case study, static pressure dropped within weeks, and fan demand began to decrease and continued declining after each condensing event.

The value of a result like this is that it is expressed in numbers facility teams already track. Static pressure across the coil and fan speed are trended by most building automation systems, which makes them a reasonable baseline for any team evaluating coil treatment.

Putting it into practice

Teams that want to address fouling and odor systematically can start with the air handlers that already generate the most work orders or complaints. Establish a baseline using coil pressure drop, fan speed, or fan demand, leaving air conditions and complaint logs. Inspect intake locations against nearby odor sources. Then decide which combination of measures fits each unit, whether that means intake changes, a cleaning schedule, continuous on-coil treatment, or some mix of the three.

Tracking the same measurements after any change gives engineering leadership a clear record of what worked, which is the documentation that supports the next capital request.